CH-1 · 500 kW water-cooled screw chiller · R-134a
Chiller digital twin
SimulatorClock --:--
No active alarmsEvery reading matches the healthy model.
Normalmatches the healthy modelWatchDegradedAlarm
| Point | Now | Expected | Status | Low | High |
|---|
How the twin judges health
Every reading is compared with what a healthy chiller would show in the same water at the same load, using the same physics the drawing runs on: R-134a saturation, approaches that grow with load, and a compressor at 70% of the Carnot limit. The gap sets the colour: normal, watch, degraded or alarm. Faults that come from outside the chiller, like a tower that stops cooling, are judged against the outdoor wet-bulb and booked to the tower, not the chiller.
Connect real data
Open the page with ?feed=https://your-gateway/latest.json and the twin polls that URL every 5 s instead of running the simulator. It expects one reading, or a list, with these fields:
t(ISO time),chw_supply_c,chw_return_c,chw_flow_lscw_in_c,cw_out_c,cw_flow_ls,outdoor_wb_cevap_bar_g,cond_bar_g,suction_superheat_k,subcooling_k,discharge_ccomp_rpm,motor_a,power_kw,vibration_mm_s